Description
Schneider Electric PM5110 power meter 96x96 METSEPM5110
The device is a flush mount energy meter with a 96mm x 96mm backlit LCD display. The meter ensures 0.5S accuracy class according to IEC 62053-22 and 64 samples per cycle. The device measures energy, active and reactive power, voltage, current, frequency, power factor and up to the 15th harmonic. The meter operates on a 50 or 60 Hz mains and accepts supply voltages of 100 to 415 V AC and 125 to 250 V DC. The rated line current for this meter is 1A or 5A input and supports single-phase and neutral, three-phase, or three-phase and neutral configurations. The measurement voltage range between phases is 35 to 690 V AC, 47 to 63 Hz. The measurement range between phase and neutral is 20 to 400VAC, 47 to 63 Hz. The communication protocol consists of by Modbus RTU and ASCII 2 cables with RS485 port. The meter also features a digital pulse output and 33 configurable alarms. Product Dimensions: Width 3.78 inches (96 mm), Depth 2.83 inches (72 mm), Height 3.78 inches (96 mm); weight 13.4 oz (380 g).
Technical data
Range
PowerLogic
Product name
PowerLogic PM5000
Device name
PM5110
Product type
Measuring instrument
Technical characteristics
power quality analysis
Up to the 15th harmonic
Application
Energy monitoring
type of measurement
Current
Voltage
Frequency
Power factor
Energy
Active and reactive power
supply voltage
90...450 V AC 45...65 Hz
100 ...300 V DC
Mains frequency
50 Hz
60 Hz
Rated current [In]
1 A
5 A
type of network
1P + N
3P + N
3P
power absorbed in VA
11 VA at 415 V
local signaling
80 ms 120 V AC typical
100 ms 230 V AC typical
100 ms 415 V AC typical
50 ms 125 V DC typicaldisplay type
Monochrome graphic LCD
display resolution
128 x 128
sampling rate
64 samples/ cycle
current measurement
50…8500 mA
analog input type
Voltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)
measurement voltage
35…760 V AC 45...65 Hz between phase and phase
20…440 V AC 45...65 Hz between phase and neutral
frequency measurement range
45…65 Hz
number of inputs
0
measurement precision
Active energy +/- 0.5%
Reactive energy +/- 2%
Active power +/- 0.5%
Apparent power +/- 0.5%
Frequency +/- 0.05%
Power factor +/- 0.5
Current +/- 0.5%
Voltage +/- 0.5%
Apparent energy +/- 0.5 %
Reactive power +/- 2%
precision class
Class 0.5S active energy compliant with IEC 62053-22
number of outputs
1 digital
communication port protocol
Modbus RTU and ASCII at 9.6 - 19.2 - 38.4 kbaud odd/even or none - 2 wires, 2500 V insulation
JBUS
communication port protocol
RS485
data logging
Time indication
Min/max of instantaneous values
connections - terminals
Voltage circuit: screw terminal4
Control circuit: screw terminal2
Currenttransformer: screw terminal6
I/O circuit: screw terminal6
RS485 connection: screw terminal4
Installation
Built-in
support assembly
Structure
Reference standards
UL 61010-1
CEI EN 50470-3
CEI EN 50470-1
IEC 62053-22 :2020
IEC 60529
IEC 62053-24
IEC 61557-12:2015
IEC 62053-23:2020
IEC 62052-11:2020
IEC 62052-3 1:2015
Product certifications
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
width
96 mm
depth
72 mm
height
96 mm
product weight
380 g