Description
Abb S204M-B10 S 204 M - B10 - 10kA Curve B 10A - 4P - B - 10 A 2CDS274001R0105
System pro M compact S200 circuit breakers protect installations from overloads and short circuits, ensuring reliability and safety in operations. They are available in different characteristics (B, C, D, K, Z), configurations (1P, 2P, 3P, 4P), breaking capacity (up to 25 kA at 230/400 V AC) and rated currents (up to 100 TO). All circuit breakers in the S200 range comply with CEI-EN 60898-1, CEI-EN 60947-2 and UL1077 and CSA 22.2 No. 235 standards (except the 4.5kA version), allowing use for residential, commercial applications and industrial. Can be associated with DDA 200.
series differential blocks
Technical data
Reference standards: IEC/EN 60898-1
CSA 22.2 No. 235
IEC/EN 60947-2
UL 1077
Tripping characteristic:B
Rated operating voltage: according to IEC 60898-1 400 V AC
according to IEC 60898-1 400 V
according to IEC 60947-2 440 V AC
Operating voltage: Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Minimum 12 V DC
Rated insulation voltage (Ui): according to IEC/ EN 60664-1 440 V
Impulse withstand voltage (Uimp): 4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Dielectric test voltage: 50/60 Hz , 1 min: 2 kV
Type of input voltage: AC/DC
Rated current (In) 10 A
Rated short-circuit capacity: (AC) 10 kA(230 V AC) 10 kA
(400 V AC) 10 kA
(400 V) 10 kA
Rated extreme short-circuit capacity (Icu): (230 V AC) 25 kA
(400 V AC) 15 kA
(440 V AC) 15 kA
(230 V) 25 kA
(400 V) 15 kA
Rated conditional short-circuit current (Inc ): (230 V) 15 kA
(400 V) 25 kA
Rated service short-circuit capacity (Ics): (230 V AC) 7.5 kA
Frequency (f): 50 Hz
Rated frequency (f): 50 / 60 Hz
50 ... 60 Hz
Power loss: 8.4 W
at Nominal Operating Conditions for Polo 2.1 W