Description
SIEMENS SITOP PSE200U SELECTIVITY MODULE 10A 6EP19612BA21
SITOP PSE200U 10 A 4-channel selective module input: DC 24 V/40 A output: DC 24 V/4x 10 A threshold value settable 3 ... 10 A with cumulative signaling contact.
General information:
Input
shape of the electrical network Regulated DC voltage
supply voltage with DC nominal value 24 V
input voltage with DC 22 ... 30 V
overloadability for overvoltage 35 V
input current at nominal value of the
input voltage 24 V nominal value 40 A
Output
shape of the voltage curve at the output Regulated DC voltage
formula for output voltage Ue - approx. 0.2 V
relative overall tolerance of the known voltage Corresponding to the input supply voltage
number of outputs 4
output current up to 60 °C for each output nominal value 10 A
value of trip settable for release current of
current-dependent overload
3 ... 10 A
type of trip value setting By potentiometer
product characteristic parallel connection of outputs No
type of activation of the outputs Simultaneous activation of all the outputs upon reaching the value of
supply voltage regime > 20 V, delay time of 24 ms, 100
ms or settable via DIP switch for sequential activation"load optimized"
Efficiency
efficiency [%] 99 %
power dissipation [W] at nominal value of the
output voltage at nominal value of the output current typ.10 W
Switch-off characteristic for each output
switching characteristic
● of the overcurrent switch-off IA = 1.0 ... 1.5 x set value, switch-off after approx. . 5 s
● of the current limitation IA = 1.5 x set value, shutdown after typ. 100 ms
● of immediate switch-off IA > set value and Ue < 20 V, switch-off after approx. 0.5 ms
residual current at switch-off typ. 1 mA
Reset execution via button for each output
Remote RESET function Non-floating 24 V input (signal level "high" at > 15 V)
Protection and monitoring
carrying out protection on the 15 A input for each output (not accessible)
running the display for normal operation Tricolor LED for each output: green LED for "Output switched on", yellow LED
for "Output manually switched off", red LED for "Output switched off due to overcurrent" design of switching contact for signaling function
Group signaling contact (changeover contact, loadability 0 ,1 A/DC 24 V).