Description
SIEMENS SITOP PSU200M 5 A 6EP13333BA10
SITOP PSU200M 5 A stabilized power supply input: AC 120/230 ... 500 V output: DC 24 V/5 A *Ex approval no longer available*
Input
form of the electrical network Single-phase and two-phase AC
supply voltage with AC
● initial value Setting via switch on the equipment; start from EU >90/180 V
supply voltage
● 1 at AC 120 ... 230 V
● 2 at AC 230 ... 500 V
input voltage
● 1 at AC 85 ... 264 V
● 2 at AC 176 ... 550 V
input implementation wide-range input Yes
overload capability for overvoltage 1300 Vpeak, 1.3 ms
backup operating condition due to lack of mains voltage
With Ue = 120/230 V, typ. 150 ms with Ue = 400 V
buffering time with nominal value of the output current
in case of mains voltage failure min. 25 ms
backup operating condition due to lack of
mains voltage
With Ue = 120/230 V, typ. 150 ms with Ue = 400 V
mains frequency
● 1 nominal value 50 Hz
● 2 nominal value 60 Hz
mains frequency 47 ... 63 Hz
input current
● at rated input voltage 120 V 2.2 A
● at rated input voltage 230 V 1, 2 A
● at nominal value of the input voltage 500 V 0.61 A
current limitation of the inrush current at 25 °C max. 35 A
I2t value max. 1.7 A²·s
execution of protection T 3.15 A (not accessible)
● of the mains cable Recommended thermomagnetic switch for single-phase operation: separately
from 6 A (10 A) characteristic C (B); required for two-phase operation:
thermic circuit breaker with bipolar coupling or automatic
breaker 3RV2011-1EA10 (setting to 3.8 A) or 3RV2711-1ED10 (UL
489) with 230 V, 3RV2011-1DA10 (setting on 3 A) or 3RV2711-1DD10
(UL 489) with 400/500 V
Output
shape of the voltage curve at the output regulated potential-free direct voltage
Output voltage with DC rated value 24 V
output voltage
● at output 1 with DC nominal value 24 V
relative overall voltage tolerance 3 %
relative control accuracy of output voltage