Description
Schneider-Electric TM3 8 output relay module TM3DQ8R
The product is part of the Modicon TM3 range, an offering of expansion I/O modules for Modicon M221, M241, M251 and M262. The digital output module provides 8 relay outputs with sink or source logic (positive/negative).
Presentation
Product range
Modicon TM3
Product type
Digital output module
range compatibility
Modicon M241
Modicon M251
Modicon M221
Modicon M262 - Modicon M241 - Modicon M251
Digital output type
Relay normally open
number of digital outputs 8
logic digital output
Positive or negative
digital output voltage
24 V DC for relay output
240 V AC
digital output current
2000 mA for relay output
Technical characteristicsnumber of digital I/Os 8
Current consumption
5 mA at 5 V DC Via the bus connector (in the off state)
0 mA at 24 V DC Via the connector of the bus (in the off state)
40 mA at 24 V DC Via the bus connector (in the on state)
30 mA at 5 V DC Via the bus connector (in the on state)
time response
10 ms (turn-on)
5 ms (turn-off)
Mechanical life
20000000 cycles
minimum load
10 mA at 5 V DC for relay output
local signaling
1 LED per channel (green)output status:
electrical connection
11 2.5 mm² terminal block removable screw with 5.08 mm pitch adjustment for outputs
maximum cable length between devices
Unshielded cable: <30 m for relay output
Isolation
Between output and internal logic at 2300 V AC
Between outputs at 750 V AC
Between output groups at 1500 V AC
CE marking
Mounting support
Top hat type TH35-15 rail compliant with IEC 60715
Top hat type TH35- 7.5 rail compliant with IEC 60715
plate or panel with fixing kit
height
90 mm
depth
84.6 mm
width
27.4 mm
product weight
0.11 kg
Environment
Reference standards
IEC 61131-2
Product certifications
CE
cULus
"UKCA"
RCM
EAC
cULus HazLoc
Resistance to electrostatic discharge
8 kV in air conforming to IEC 61000-4-2
4 kV on contact conforming to IEC 61000-4- 2
resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to IEC 61000 -4-3
1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
resistance to magnetic fields
30 A/m 50/60 Hz conforming to IEC 61000-4 -8
fast transient resistance
2 kV for relay output conforming to IEC 61000-4-4
surge resistance
1 kV I/O common mode conforming to IEC 61000-4-5 DC
resistance to conducted disturbances, induced by radio frequency fields
10 V 0.15...80 MHz conforming to IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) compliant with Marine specification (LR, ABS, DNV, GL)
electromagnetic emission
Radiated emissions 40 dBμV/m QP class A (10 m) at 30… 230 MHz conforming to IEC 55011
Radiated emissions 47 dBμV/m QP class A (10 m) at 230…1000 MHz conforming to IEC 55011
operating ambient temperature
-10…35 °C vertical installation
-10…55 °C horizontal installation
Storage temperature
-25…70 °C
relative humidity
10…95 %, non-condensing (in operation)
10…95 %, non-condensing (in storage)
IP protection degree
IP20 with protective cover mounted
Pollution degree 2
Operating altitude
0...2000 m
storage altitude
0…3000 m
vibration resistance
3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on panel