Description
Schneider Electric Power base - TeSys U - 12 A - Control screw terminals LUB12
TeSys U standard power base, 3 pole (3NO), 12 A/ 690 V, to be completed with a LUC control unit to form a TeSys U reversing starter controller, for 3-speed motor applications phases up to 5.5 kW at 400 V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to get an "all in one" starter controller with protection functions and basic or advanced control. It is equipped with a connection terminal block and closing shutters that cover the empty cavities. It provides a high breaking capacity Icu 50 kA at 400 V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm wide), DIN rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in combination with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), compliant with Green Premium (RoHS/REACh).
Range: TeSys
Product Name: TeSys Ultra
Device Name: LUB
Product Type : Power base with 1 direction of travel
Application: Motor control Motor protection
Number of Poles: 3P
Aptitude for Insulation: Yes
Nominal Operational Voltage [Ue]: 690 V AC for Power Circuit
Mains Frequency: 40...60 Hz
Conventional Thermal Current In Air [Ith]: 12 A
Rated Operational Current [Ie] 12 A at <= 440 V
12 A at 500 V
9 A at 690 V
Usage Category AC-43
AC-44
AC-41
Rated Breaking Capacity Service [Ics]
50 kA at 230 V
50 kA at 440 V
10 kA at 500 V
4 kA at 690 V
Auxiliary Contact Composition : 1 NO + 1 NC
Type of Auxiliary Contacts connected contact type (1 NO + 1 NC) conforming to IEC 60947-4-1
mirror contact type (1 NC) conforming to IEC 60947-1
typical current consumption
130 mA at 24 V DC I maximum during closing with LUCA, LUCB, LUCC, LUCD
140 mA at 24 V AC I maximum during closing with LUCA, LUCB, LUCC, LUCD
150 mA at 24 V DC I maximum during closing with LUCM
280 mA at 110...220 V DC I maximum during closing with LUCA, LUCB, LUCC, LUCD
280 mA at 110...240 V AC I maximum during closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V AC I maximum during closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V DC I maximum during closing with LUCA, LUCB, LUCC, LUCD
35 mA at 110...220 V DC I rms fixed with LUCA, LUCB, LUCC, LUCD
35 mA at 110...240 V AC I rms fixed with LUCA, LUCB, LUCC, LUCD
35 mA at 48...72 V AC I rms fixed with LUCA, LUCB, LUCC, LUCD
35 mA at 48...72 V DC I rms fixed with LUCA, LUCB, LUCC, LUCD
60 mA at 24 V DC I rms fixed with LUCA, LUCB, LUCC, LUCD
70 mA at 24 V AC I rms fixed with LUCA, LUCB , LUCC, LUCD
70 mA at 24 V DC I rms fixed with LUCM
heat dissipation
2 W for control loop with LUCA, LUCB, LUCC, LUCD
1.7 W per control circuit with LUCM
Safety reliability level
B10d = 1369863 cycles Contactor with rated load compliant with EN/ISO 13849-1
B10d = 20000000 cycles Contactor with mechanical load compliant with EN /ISO 13849-1
operating time
35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM for control circuit
50 ms at >= 72 V closing with LUCA , LUCB, LUCC, LUCD for control circuit
60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD for circuit control circuit
75 ms closing with LUCM for control circuit
Mechanical life
15 Mcycles
Maximum operating speed
3600 cycles/h
Product certifications
CE
UL
CSA
CCC
EAC
ASEFA
ATEX
Marina
Standards
EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase spreader
CSA C22.2 No 60947-4-1, with phase spreader phase
Rated insulation voltage [Ui]
690 V conforming to IEC 60947-6-2 (pollution degree 3)
600 V conforming to UL 60947-4-1
600V compliant with CSA C22.2 No 60947-4-1
Rated impulse withstand voltage [Uimp]
6 kV conforming to IEC 60947-6-2
safe circuit separation
400 V SELV between auxiliary and control circuits conforming to IEC 60947-1 appendix N
400 V SELV between auxiliary or control circuit and main circuit conforming to IEC 60947-1 appendix N
type of fixing
Clip-on (DIN rail)
Screw fixed (Plate)
connections - terminals
Control circuit: screw fixing terminals 1 cables 0 ,34…1.5 mm² flexible with cable termination
Control circuit: screw fixing terminals 1 cables 0.75…1.5 mm² flexible without cable termination
Control circuit: screw fixing terminals 1 cables 0.75…1.5 mm² rigid
Control circuit: screw fixing terminals 2 cables 0.34…1.5 mm² flexible with cable termination
Control circuit: screw fixing terminals 2 cables 0.75…1.5 mm² flexible without cable termination
Control circuit: screw fixing terminals 2 cables 0.75…1.5 mm² rigid
Power circuit: screw fixing terminals 1 cables 1 …10 mm² rigid
Power circuit: screw fixing terminals 1 cable 1…6 mm² flexible with cable termination
Power circuit: screw fixing terminals 1 cable 2.5…10 mm² flexible without cable termination
Power circuit: screw fixing terminals 2 cables 1…6 mm² flexible with cable termination
Power circuit: screw fixing terminals 2 cables 1…6 mm² rigid
Power circuit: screw fixing terminals screw fixing 2 cables 1.5…6 mm² flexible without cable termination
tightening torque
Control circuit: 0.8…1.2 Nm flat screwdriver 5 mm
Circuit control: 0.8…1.2 Nm Philips no 1 screwdriver 5 mm
Power circuit: 1.9…2.5 Nm flat screwdriver 6 mm
Power circuit: 1.9…2.5 Nm Philips No 2 screwdrivers 6 mm
Power circuit: 1.9…2.5 Nm pozidriv No 2 screwdrivers 6 mm
width
45 mm
height
154 mm
depth
126 mm
product weight
0.9 kg
Compatibility code
LUB