Description
Schneider Electric LC1DT60AM7
TeSys LC1D contactor, 4-pole, AC1- 440V AC, 60A, 220V AC.
Technical data
Code compatibility
LC1D
Composition contact pole
4 NO
Protective cover
With conventional thermal current in open air [Ith]10 A (at 60 °C) for signal circuit
60 A (at 60 °C) for power circuit
Nominal closing power Irms
140 A AC for signal circuit conforming to IEC 60947-5-1
250 A DC for signaling circuit conforming to IEC 60947-5-1
800 A at 440 V for power circuit conforming to IEC 60947
nominal switching capacity
800 A at 440 V for power circuit conforming to IEC 60947
Short-term rated permissible current [Icw]
320 AT 40 °C - 10 s for power circuit
720 AT 40 °C - 1 s for power circuit
72 AT 40 °C - 10 min for power circuit
165 AT 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signal circuit
140 A - 100 ms for signal circuit
Associated fuse gauge
10 A gG for signalling circuit conforming to IEC 60947-5-1
80 A gG at <= 690 V coordination Type 1 for power circuit
80 A gG at <= 690 V coordination Type 2 for power circuit
average impedance
1.6 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole
5.8 W AC-1
Rated isolation voltage [Ui]
600V CSA Certified Power Circuit:
600 V UL certified power circuit:
690 V according to IEC 60947-1 signal circuit:
600 V CSA circuit signaling certificate:
600 V UL certified circuit signaling:
690 V according to IEC 60947-4-1 power circuit:
Category of overvoltage
III
Degree of pollution
3
Nominal pulse-holding voltage [Uimp]
6 kV in accordance with IEC 60947
Level of safety reliability
B10d = 1369863 cycles Contactor with rated load according to EN/ISO 13849-1
B10d = 20000000 cycles Contactor with mechanical load in accordance with EN/ISO 13849-1
Mechanical durability
6 Mcicli
electrical durability
1.4 Mcicli 60 A AC-1 at Eu <= 440 V
type of control circuit
AC at 50/60 Hz