1SAE231111R0131 | Abb ESB25-31N-01

Description

Abb ESB25-31N-01 1SAE231111R0131

Modular contactors - Automatic control - 3 n.o. contacts + 1 n.c. contact

Technical data

  • Rated operating voltage:
    Main Circuit 220 V DC
    Main Circuit 400 V AC
  • Nominal control circuit voltage (Uc):
    24V
  • Nominal frequency (f):
    Control Circuit 400 Hz
    Control Circuit 50 Hz
    Control Circuit 60 Hz
    DC Control Circuit
    Main Circuit 50 Hz
    Main Circuit 60 Hz
    Main Circuit DC
  • Rated operating current AC-1 (Ie):
    (NC) 25 A
    (NO) 25 A
  • Rated operating current AC-3 (Ie):
    (230 V) Single Phase, NC 6 A
    (230 V) Single Phase, NO 9 A
    (400 V) Three Phase, NO 9 A
  • Rated operating current AC-1 (Pe):
    (230 V) Single Phase, NC 5.8 kW
    (230 V) Single Phase, NO 5.8 kW
    (400 V) Three Phase, NO 17.3 kW
  • Rated operating current AC-3 (Pe):
    (230 V) Single Phase, NC 1.3 kW
    (230 V) Single Phase, NO 1.3 kW
    (400 V) Three Phase, NO 4 kW
  • Rated operating current AC-7a (Ie):
    (NC) 25 A
    (NO) 25 A
  • Rated operating current AC-7a (Pe):
    (230 V) Single Phase, NC 5.8 kW
    (230 V) Single Phase, NO 5.8 kW
    (400 V) Three Phase, NO 17.3 kW
  • Rated operating current AC-7b (Ie):
    (230 V) Single Phase, NC 6 A
    (230 V) Single Phase, NO 9 A
    (400 V) Three Phase, NO 9 A
  • Rated operating current AC-7b (Pe):
    (230 V) Single Phase, NC 0.9 kW
    (230 V) Single Phase, NO 1.3 kW
    (400 V) Three Phase, NO 4 kW
  • Recommended screwdriver:
    Control Circuit Pozidriv 1
    Main Circuit Pozidriv 1
  • Impulse withstand voltage (Uimp):
    6 kV
  • Rated insulation voltage (Ui):
    500V
  • Cable sections - main circuit:
    Flexible with Ferrule 1x 1.5 ... 10 mm²
    Flexible with Ferrule 2x 1.5 ... 2.5 mm²
    Flexible with Insulated Ferrule 1x 1.5 ... 10 mm²
    Flexible with Insulated Ferrule 2x 1.5 mm²
    Flexible 1x 1.5 ... 10 mm²
    Flexible 2x 1.5 ... 4 mm²
    Rigid 1x 1.5 ... 10 mm²
    Rigid 2x 1.5 ... 4 mm²
  • Control circuit-cable sections:
    Flexible with Ferrule 1x 1 ... 2.5 mm²
    Flexible with Ferrule 2x 0.75 ... 1 mm²
    Flexible with Insulated Ferrule 1x 1 ... 2.5 mm²
    Flexible with Insulated Ferrule 2x 0.75 . .. 1 mm²
    Flexible 1x 1 ... 4.0 mm²
    Flexible 2x 1 ... 2.5 mm²
    Rigid 1x 1 ... 4 mm²
    Rigid 2x 1 ... 2.5 mm²
  • Tightening torque:
    Control Circuit 0.9 N m
    Main Circuit 1 N m
  • Cable stripping length:
    Control Circuit 7 mm
    Main Circuit 10 mm
  • Degree of protection:
    IP20
  • Electrical life:
    AC-1 (NC) 50000 cycle (i)
    AC-1 (NO) 130000 cycle (i)
    AC-3 (NC) 340000 cycle (i)
    AC-3 (NO ) 500000 cycle (i)
    AC-7a (NC) 50000 cycle (i)
    AC-7a (NO) 130000 cycle (i)
    AC-7b (NC) 340000 cycle (i)AC-7b (NO) 500000 cycle (i)
  • Mechanical durability:
    1000000 cycle (i)
  • Number of poles:
    4
  • Number of NC auxiliary contacts:
    0
  • Number of auxiliary contacts NO:
    0
  • Number of NC main contacts:
    1
  • Number of main NA contacts:
    3
  • Width in number of modular intervals:
    2
  • Pollution degree:
    3
  • Reference standards:
    IEC/EN 60947-1
    IEC/EN 60947-4-1
    IEC/EN 61095
    UL 60947-1
    UL 60947-4-1

UL/CSA Technical Department

  • Maximum operating voltage UL/CSA:
    Main Circuit 480 V AC
  • UL/CSA Scope:
    (220 ... 240 V AC) Single Phase, NC 1 Hp
    (220 ... 240 V AC) Single Phase, NO 1 Hp
    (220 ... 240 V AC) Three Phases, NO 3 Hp
    (440 ... 480 V AC) Single Phase, NC 2 Hp
    (440 ... 480 V AC) Single Phase, NO 2 Hp
    (440 ... 480 V AC) Three Phases , NO 5 Hp
  • UL/CSA main circuit cable cross sections:
    Solid 16-8 AWG
    Stranded 16-8 AWG
  • UL/CSA control circuit cable cross sections:
    Solid 16-10 AWG
    Stranded 16-10 AWG
  • UL/CSA tightening torque:
    Control Circuit 8 in lb
    Main Circuit 9 in lb
Product form

IN STOCK

SKU: ESB2531N01
Barcode: 4013614517662

€44,40

    • STANDARD RETURN
    • QUICK DELIVERY ASSURED
    • HS CODE: 85365080
      SPECIFICATIONS

    • Tensione nominale di esercizio - 220...400 V
    • Corrente nominale di esercizio - 25 A
    • Tensione nominale di comando - 24...24 V
    • Tipo di tensione di esercizio - AC / DC
    • Tipo di tensione di comando - AC / DC

      DOCUMENTATION

    Description

    Abb ESB25-31N-01 1SAE231111R0131

    Modular contactors - Automatic control - 3 n.o. contacts + 1 n.c. contact

    Technical data

    • Rated operating voltage:
      Main Circuit 220 V DC
      Main Circuit 400 V AC
    • Nominal control circuit voltage (Uc):
      24V
    • Nominal frequency (f):
      Control Circuit 400 Hz
      Control Circuit 50 Hz
      Control Circuit 60 Hz
      DC Control Circuit
      Main Circuit 50 Hz
      Main Circuit 60 Hz
      Main Circuit DC
    • Rated operating current AC-1 (Ie):
      (NC) 25 A
      (NO) 25 A
    • Rated operating current AC-3 (Ie):
      (230 V) Single Phase, NC 6 A
      (230 V) Single Phase, NO 9 A
      (400 V) Three Phase, NO 9 A
    • Rated operating current AC-1 (Pe):
      (230 V) Single Phase, NC 5.8 kW
      (230 V) Single Phase, NO 5.8 kW
      (400 V) Three Phase, NO 17.3 kW
    • Rated operating current AC-3 (Pe):
      (230 V) Single Phase, NC 1.3 kW
      (230 V) Single Phase, NO 1.3 kW
      (400 V) Three Phase, NO 4 kW
    • Rated operating current AC-7a (Ie):
      (NC) 25 A
      (NO) 25 A
    • Rated operating current AC-7a (Pe):
      (230 V) Single Phase, NC 5.8 kW
      (230 V) Single Phase, NO 5.8 kW
      (400 V) Three Phase, NO 17.3 kW
    • Rated operating current AC-7b (Ie):
      (230 V) Single Phase, NC 6 A
      (230 V) Single Phase, NO 9 A
      (400 V) Three Phase, NO 9 A
    • Rated operating current AC-7b (Pe):
      (230 V) Single Phase, NC 0.9 kW
      (230 V) Single Phase, NO 1.3 kW
      (400 V) Three Phase, NO 4 kW
    • Recommended screwdriver:
      Control Circuit Pozidriv 1
      Main Circuit Pozidriv 1
    • Impulse withstand voltage (Uimp):
      6 kV
    • Rated insulation voltage (Ui):
      500V
    • Cable sections - main circuit:
      Flexible with Ferrule 1x 1.5 ... 10 mm²
      Flexible with Ferrule 2x 1.5 ... 2.5 mm²
      Flexible with Insulated Ferrule 1x 1.5 ... 10 mm²
      Flexible with Insulated Ferrule 2x 1.5 mm²
      Flexible 1x 1.5 ... 10 mm²
      Flexible 2x 1.5 ... 4 mm²
      Rigid 1x 1.5 ... 10 mm²
      Rigid 2x 1.5 ... 4 mm²
    • Control circuit-cable sections:
      Flexible with Ferrule 1x 1 ... 2.5 mm²
      Flexible with Ferrule 2x 0.75 ... 1 mm²
      Flexible with Insulated Ferrule 1x 1 ... 2.5 mm²
      Flexible with Insulated Ferrule 2x 0.75 . .. 1 mm²
      Flexible 1x 1 ... 4.0 mm²
      Flexible 2x 1 ... 2.5 mm²
      Rigid 1x 1 ... 4 mm²
      Rigid 2x 1 ... 2.5 mm²
    • Tightening torque:
      Control Circuit 0.9 N m
      Main Circuit 1 N m
    • Cable stripping length:
      Control Circuit 7 mm
      Main Circuit 10 mm
    • Degree of protection:
      IP20
    • Electrical life:
      AC-1 (NC) 50000 cycle (i)
      AC-1 (NO) 130000 cycle (i)
      AC-3 (NC) 340000 cycle (i)
      AC-3 (NO ) 500000 cycle (i)
      AC-7a (NC) 50000 cycle (i)
      AC-7a (NO) 130000 cycle (i)
      AC-7b (NC) 340000 cycle (i)AC-7b (NO) 500000 cycle (i)
    • Mechanical durability:
      1000000 cycle (i)
    • Number of poles:
      4
    • Number of NC auxiliary contacts:
      0
    • Number of auxiliary contacts NO:
      0
    • Number of NC main contacts:
      1
    • Number of main NA contacts:
      3
    • Width in number of modular intervals:
      2
    • Pollution degree:
      3
    • Reference standards:
      IEC/EN 60947-1
      IEC/EN 60947-4-1
      IEC/EN 61095
      UL 60947-1
      UL 60947-4-1

    UL/CSA Technical Department

    • Maximum operating voltage UL/CSA:
      Main Circuit 480 V AC
    • UL/CSA Scope:
      (220 ... 240 V AC) Single Phase, NC 1 Hp
      (220 ... 240 V AC) Single Phase, NO 1 Hp
      (220 ... 240 V AC) Three Phases, NO 3 Hp
      (440 ... 480 V AC) Single Phase, NC 2 Hp
      (440 ... 480 V AC) Single Phase, NO 2 Hp
      (440 ... 480 V AC) Three Phases , NO 5 Hp
    • UL/CSA main circuit cable cross sections:
      Solid 16-8 AWG
      Stranded 16-8 AWG
    • UL/CSA control circuit cable cross sections:
      Solid 16-10 AWG
      Stranded 16-10 AWG
    • UL/CSA tightening torque:
      Control Circuit 8 in lb
      Main Circuit 9 in lb
    • Warranty

      12 month warranty. For more information visit Termini e Condizioni

    • Return Policy

      Standard. For more information visit Terms and Conditions

    • E-mail

      Contact us via email info@dmstechmart.com and we will try to respond to you as quickly as possible

    • Telephone

      We are at your disposal for further information by telephone at +39 0230567159 from Monday to Friday from 09.00 to 18.00 (CET).

    Recently viewed products

    © 2024 DMSTECHMART, Powered by Shopify

      • American Express
      • Apple Pay
      • Google Pay
      • Maestro
      • Mastercard
      • PayPal
      • Shop Pay
      • Union Pay
      • Visa

      Login

      Forgot your password?

      Don't have an account yet?
      Create account